HP (Hewlett-Packard) 651176-002 ユーザーズマニュアル

ページ / 80
 
UPS operations  42 
 
NOTE:
  If the On and Off buttons are simultaneously pressed, the Off button has priority over the 
On button. 
  
    
Button 
Assertion 
time 
Audible alarm  Mode before 
assertion 
Utility 
present ? 
Action 
On 
0.5 seconds  Every 0.5 seconds 
until the button is 
released 
Standby 
Yes 
Energizes the load and 
resets the bypass entry count 
to 0 
 
 
 
Operate 
Yes 
Resets the bypass entry count 
to 0 
 
 
 
Auto-Bypass 
Yes 
Clears the UPS On audible 
alarms, resets the bypass 
entry count to 0, and 
attempts to transfer to 
Operate mode 
 
 
 
Converter Off 
Yes 
Clears the UPS On audible 
alarms, resets the bypass 
entry count to 0, and 
attempts to transfer to 
Operate mode 
Off 
3 seconds 
Every 0.5 seconds 
until the button is 
released 
Operate 
Yes 
Transfers to Standby mode, 
and power to the load 
ceases 
 
 
 
Standby 
Yes 
No action 
 
 
 
Battery 
No 
Powers down the UPS, and 
power to the load ceases 
 
 
 
Auto-bypass 
Yes or No 
Transfers to Standby mode 
or Converter Off mode, and 
power to the load ceases 
Self Test 
0.5 seconds 
 
Any 
Yes or No 
Silences audible alarms after 
0.5 seconds 
 
3 seconds 
Continuously 
Any 
Yes or No 
Initiates a self-test 
Battery Start  0.5 seconds 
 
Any 
Yes or No 
No action 
Battery Start 
and On 
3 seconds 
Continuously 
UPS off 
No 
Transfers to battery power, 
and begins powering the 
load 
On and Self 
Test 
3 seconds 
Continuously 
Any 
Yes or No 
Enters or exits Configuration 
mode 
 
 
Configuring the UPS 
The UPS automatically detects the number of ERMs connected. 
In Configure mode, the LED front panel display changes function to enable modification of the UPS 
parameters. Each LED is associated with a different parameter. 
     
Available settings 
Parameter   
Associated LED 
Explanation (when LED is illuminated) 
Nominal voltage 
setting 
100/204 Nom  Self Test 
Nominal output voltage is 100 V for a low 
voltage model and 204 V for a high voltage 
model