Specifications  63 
Feature 
Specification 
Charging 
Complete charge takes no more than 48 hours. After 
approximately 3 hours, the batteries reach 80% charge at default 
nominal utility voltage and no load. 
 
 
High-voltage UPS battery runtimes 
     
Load, percent 
Estimated battery 
runtime 
Runtime with one ERM 
Runtime with two ERMs 
20 
40 minutes 
125 minutes 
225 minutes 
50 
12 minutes 
50 minutes 
89 minutes 
80 
6 minutes 
30 minutes 
54 minutes 
100 
4 minutes 
24 minutes 
43 minutes 
     
 
Low-voltage UPS battery runtimes 
     
Load, percent 
Estimated battery 
runtime 
Runtime with one ERM 
Runtime with two ERMs 
20 
45 minutes 
142 minutes 
256 minutes 
50 
15.5 minutes 
55 minutes 
99 minutes 
80 
7 minutes 
34 minutes 
60 minutes 
100 
5 minutes 
26 minutes 
47 minutes 
     
 
Environmental specifications 
   
Feature 
Specification 
Operating temperature  10°C to 40°C (50°F to 104°F); UL-tested at 25°C 
(77°F) 
Nonoperating 
temperature 
-15°C to 40°C (-5°F to 104°F) 
Relative humidity 
20% to 80%; noncondensing 
Operating altitude 
Up to 3,000 m (9,842 ft) above sea level 
Nonoperating altitude 
15,000 m (49,212 ft) above sea level 
Audible noise 
Less than 45 dBA, normal operation 
Less than 50 dBA, on battery power 
 
 
REPO port specifications 
The REPO port meets the requirements of NFPA 70 and NEC Articles 645-10 and 645-11 for a 
Disconnecting Means.