4.3  Front Panel Settings
Listed below are the default settings of the primary UPS parameters.
Settings
Options
Default
Remarks
1) O/P VOLT SET 
100V/110V/115V/120V/127V
120V 
120V (FOR LV series)
(Output Voltage Set)
208/220/230/240 Vac
230V 
230V (FOR HV series)
2) I/P FREQ SET
±2%
±5%
Input Frequency range
(Input Frequency Set)
±5%
in Free Run mode.
±7%
3) I/P BYPASS SET
±10%
+10/-15%
(Input Bypass Setting)
+10% -15%
+15/-20%
4) FREE RUN SET
ON / OFF
ON
If ON, enable UPS runs on 
unsynchronized Mode.
For example, if input 
frequency 55Hz, output 
frequency will stay at 60Hz. 
If OFF, disable UPS runs on 
unsynchronized mode.
For example, if input 
frequency 55Hz, UPS will go 
to Battery mode.
5) HE MODE SET
ON / OFF
OFF
If ON, enable UPS runs on 
high efficiency mode.  
Bypass mode is on when 
power flows at 95% or lower.
If OFF, disable UPS runs on 
high efficiency mode.  
Bypass mode is on when 
power flows at 85% or lower.
6) MANUAL BYPASS
ON / OFF
OFF
If ON, enable UPS switch to 
Bypass mode immediately.
Input Voltage range when 
Bypass mode is on.