4.3 Front Panel Settings
Listed below are the default settings of the primary UPS parameters.
Settings
Options
Default
Remarks
1) O/P VOLT SET
100V/110V/115V/120V/127V
120V
120V (FOR LV series)
(Output Voltage Set)
208/220/230/240 Vac
230V
230V (FOR HV series)
2) I/P FREQ SET
±2%
±5%
Input Frequency range
(Input Frequency Set)
±5%
in Free Run mode.
±7%
3) I/P BYPASS SET
±10%
+10/-15%
(Input Bypass Setting)
+10% -15%
+15/-20%
4) FREE RUN SET
ON / OFF
ON
If ON, enable UPS runs on
unsynchronized Mode.
unsynchronized Mode.
For example, if input
frequency 55Hz, output
frequency will stay at 60Hz.
frequency 55Hz, output
frequency will stay at 60Hz.
If OFF, disable UPS runs on
unsynchronized mode.
unsynchronized mode.
For example, if input
frequency 55Hz, UPS will go
to Battery mode.
frequency 55Hz, UPS will go
to Battery mode.
5) HE MODE SET
ON / OFF
OFF
If ON, enable UPS runs on
high efficiency mode.
Bypass mode is on when
power flows at 95% or lower.
high efficiency mode.
Bypass mode is on when
power flows at 95% or lower.
If OFF, disable UPS runs on
high efficiency mode.
Bypass mode is on when
power flows at 85% or lower.
high efficiency mode.
Bypass mode is on when
power flows at 85% or lower.
6) MANUAL BYPASS
ON / OFF
OFF
If ON, enable UPS switch to
Bypass mode immediately.
Bypass mode immediately.
Input Voltage range when
Bypass mode is on.
Bypass mode is on.