Wiring the 480V Power Supply
 9200 Power Supply Retrofit Instructions
Page 4
Wiring the 480V Power Supply
480V Power Supply
Connect one phase to the L1 terminal and the other phase to the L2 terminal. You 
can use the same wires from the grid that the voltage inputs use (see diagram 
above). 
The power supply G (ground) terminal must be connected to the same point as the 
meter  
terminal. 
Protective Fuses
The 480V power supply requires 100 mA fuses on the L1 and L2 terminals. These 
should be IEC type T slow blow fuses.
N
OTE
100 mA fuses can be shared with the voltage inputs.
Powering Up the Meter
After the power supply is attached to the meter, and its wiring is connected: 
1.
Reconnect and energize all wiring that was disconnected when the meter was 
prepared for power supply installation.
2.
Power up the meter and verify correct operation.   
100 mA fuses 
on L1 and L2
Use18 to 14 AWG 
(0.8mm
2
 to 2.1mm
2
) wires
Connections to the 
L1 and L2 terminals 
can come from V1 
and V2
Use18 to 14 AWG 
(0.8mm
2
 to 2.1mm
2
) wire