GE LP 33 ユーザーズマニュアル

ページ / 57
Modifications reserved 
Page 7/57 
OPM_LPS_3UO_30K_40K_0US_V010.doc 
Operating Manual LP 33 Series 30 & 40 kVA 
SAVE THESE INSTRUCTIONS 
 
This manual contains important instructions for models LP 33 Series / 10 & 20 kVA that should 
be followed during installation and maintenance of the UPS and battery. 
 
 
GENERAL 
 
-  Move the UPS in an upright position in its original package to the final destination 
room. 
Check for sufficient floor and elevator loading capacity. 
Check the integrity of the UPS equipment carefully. 
If you notice visible damage, do not install or start the UPS. Contact the nearest Service 
Center immediately. 
- WARNING! RISK OF ELECTRICAL SHOCK: Do not remove covers; there are no user 
serviceable parts inside. 
-  After switching off takes 5 minutes for the DC capacitors to discharge because a lethally 
high voltage remains at the terminals of the electrolytic capacitors. 
All maintenance and service work should be performed by qualified service personnel. 
The UPS contains its own energy source (battery). 
-  The field-wiring terminals may be electrically live, even when the UPS is disconnected 
from the utility. 
Dangerous voltages may be present during battery operation. 
The battery must be disconnected during maintenance or service work. 
This UPS contains potentially hazardous voltages. 
Be aware that the inverter can restart automatically after the utility voltage is restored. 
 
 
STORAGE 
 
-  Store the UPS in a dry location; storage temperature must be within -13°F  (-25°C) to 
131°F (55°C). 
-  If the unit is stored for a period exceeding 3 months, the battery must be recharged 
periodically (time depending on storage temperature). 
 
 
BATTERY 
 
The battery-voltage is dangerous for person’s safety. 
When replacing the battery, use the same number, voltage (V) and capacity (Ah). 
Proper disposal or recycling of the battery is required. 
Refer to your local codes for disposal requirements. 
-  Never dispose of battery in a fire: They may explode. 
Do not open or mutilate battery: Their contents (electrolyte) may be extremely toxic. 
If exposed to electrolyte, wash immediately with plenty of water. 
Avoid charging in a sealed container. 
-  Never short circuit battery. When working with battery, remove watches, rings or other 
metal objects, and only use insulated tools.