Hitachi L100 ユーザーズマニュアル

ページ / 192
L100 Inverter
Conf
igur
ing
Dr
iv
e P
a
ra
m
e
ters
3–17
Jump Frequencies – Some motors or machines exhibit resonances at particular 
speed(s), which can be destructive for prolonged running at those speeds. The inverter 
has up to three jump frequencies as shown in the graph. The hysteresis around the jump 
frequencies causes the inverter output to skip around the sensitive frequency values
Jump frequencies
A 63
A 64
Output
frequency
Frequency command
A 64
A 66
A 66
A 68
A 68
A 65
A 67
Hysteresis values
0
“A” Function
Run 
Mode 
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FE 
(CE)
–FU 
(UL)
–FR 
(Jpn)
Units
A_63,
A_65,
A_67
Jump (center) 
frequency setting
Up to 3 output frequencies can 
be defined for the output to 
jump past to avoid motor 
resonances (center frequency)
Range is 0.0 to 360.0 Hz
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Hz
JUMP F1  000.0Hz
JUMP F2  000.0Hz
JUMP F3  000.0Hz
A_64,
A_66,
A_68
Jump (hysteresis) 
frequency width setting
Defines the distance from the 
center frequency at which the 
jump around occurs
Range is 0.0 to 10.0 Hz
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Hz
JUMP W1  00.50Hz
JUMP W2  00.50Hz
JUMP W3  00.50Hz