Emerson MODBUS 485 ユーザーズマニュアル
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
114
Table 39
Liebert STS2
™
, Liebert STS2/PDU
™
- Input and Holding - STS2
Controller
STS2
Liebert Products
Liebert STS2
Liebert STS2/PDU
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Status Points (View)
Total Transfer Count
Total Transfer Count
—
40001
1
—
—
Preferred Source
—
40002
1
—
1=Source 1, 2=Source 2
Active Source
—
40003
1
—
1=Source 1, 2=Source 2
Source 1 Volts A-B
—
40004
1
—
V
Source 1 Volts B-C
—
40005
1
—
V
Source 1 Volts C-A
—
40006
1
—
V
Source 1 Current A
—
40007
1
—
A
Source 1 Current B
—
40008
1
—
A
Source 1 Current C
—
40009
1
—
A
Source 1 Frequency
—
40010
1
10
Hz
Source 2 Volts A-B
—
40011
1
—
V
Source 2 Volts B-C
—
40012
1
—
V
Source 2 Volts C-A
—
40013
1
—
V
Source 2 Current A
—
40014
1
—
A
Source 2 Current B
—
40015
1
—
A
Source 2 Current C
—
40016
1
—
A
Source 2 Frequency
—
40017
1
10
Hz
Output kW
—
40018
1
—
kW
Output kVA
—
40019
1
—
kVA
CB 1 Status
—
40024
1
—
Bit 0
CB 2 Status
—
40024
1
—
Bit 1
CB 3 Status
—
40024
1
—
Bit 2
CB 3A Status
—
40024
1
—
Bit 3
CB 4 Status
—
40024
1
—
Bit 4
CB 5 Status
—
40024
1
—
Bit 5
CB Spare 1 Status
—
40024
1
—
Bit 6
CB Spare 2 Status
—
40024
1
—
Bit 7
CB 7 Status
—
40024
1
—
Bit 8
CB 8 Status
—
40024
1
—
Bit 9
Auto Xfer Enabled
—
40025
1
—
Bit 0
Has Dual Out Breakers
—
40025
1
—
Bit 1
Has PDU Equipped
—
40025
1
—
Bit 2
Has 4 pole Switch
—
40025
1
—
Bit 3
Has Shunt Trip
—
40025
1
—
Bit 4
Has Wye Out Xfmr
—
40025
1
—
Bit 5
Has Rmt Sorce Sel
—
40025
1
—
Bit 6
Manual I peak Reset
—
40025
1
—
Bit 7
Auto Restart Enabled
—
40025
1
—
Bit 8