Emerson MODBUS 485 ユーザーズマニュアル
Modbus 485 and Modbus IP Protocols - UPS Systems
195
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 66
Liebert Series 300
™
UPS - Input and Holding
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Number of Input Lines
30004
40004
1
—
Bits 12 - 15
Number of Bypass Lines
30004
40004
1
—
Bits 4 - 7
Number of Output Lines
30004
40004
1
—
Bits 8 - 11
Number of SubModules
30009
40009
1
—
—
Load Circuit Present
30013
40013
1
—
There are 16 possible Load Circuits. Each bit
represents 1 Load Circuit. Load Circuit 1 is bit
0, Load Circuit 2 is bit 1 and so on. If the bit is
1, then the Load Circuit is supported.
Nominal Power Rating
30021
40021
2
—
VA
Nominal Input Voltage
30027
40027
1
—
V
Nominal Output Voltage
30028
40028
1
—
V
Nominal Static Bypass Switch
Voltage
30029
40029
1
—
V
Nominal Input Current
30030
40030
1
—
A
Nominal Input Frequency
30031
40031
1
10
Hz
Nominal Output Frequency
30032
40032
1
10
Hz
Nominal Power Factor
30033
40033
1
100
-
Nominal Battery Voltage
30034
40034
1
—
V
Device Low Battery Time
30053
40053
1
—
Minutes
Load (Apparent Power)
30102
—
2
—
VA
Load (Real Power)
30104
—
2
—
W
Load / Capacity
30106
—
1
—
%
Input Frequency
30107
—
1
10
Hz
Output Frequency
30108
—
1
10
Hz
Bypass Frequency
30109
—
1
10
Hz
Battery Charge Status
30112
—
1
—
1 - 100% Charged
2 - Less than 100% Charged
Battery Voltage
30113
—
1
—
V
Battery Current
30114
—
1
—
A
Battery Time Remaining
30115
—
1
—
Minutes
Battery Charge Percentage
30116
—
1
—
%
Battery Test Result
30130
—
1
—
1 - Unknown
2 - Passed
3 - Failed
4 - In Progress
5 - System Failure
6 - Inhibited
Input Voltage L1
30153
—
1
—
V
Input Current
30154
—
1
—
A
Bypass Voltage L1
30159
—
1
—
V
Bypass Current L1
30160
—
1
—
A
Output Voltage L1
30163
—
1
—
V
Output Current L1
30164
—
1
—
A
Input Voltage L2
30203
—
1
—
V
Input Current L2
30204
—
1
—
A
Bypass Voltage L2
30209
—
1
—
V