HP (Hewlett-Packard) A6584A ユーザーズマニュアル

ページ / 120
 
HP UPS Management Module web interface  65 
Events tab 
This screen enables administrators to define the event notifications, emails, or SNMP traps the 
management module sends for each event. 
 
To configure the event notifications: 
1. 
For each event description listed, select the Enabled checkbox to indicate that email notifications or 
SNMP traps are sent for that event. To enable all events, click the Email checkbox and the SNMP 
Trap checkbox at the top of each column.  
2. 
For each email and SNMP trap enabled, enter the number of minutes that should pass between the 
occurrence of an alert condition and the sending of the notification. 
  
 
NOTE:
  If the event clears before the delay time has expired, then the event notification is not 
sent. 
  
3. 
Do one of the following: 
Click Save Settings to save the information. 
Click Undo Changes to undo the changes. 
Click Help to view online help.