Interface Submodules
13-46
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
13.7.6
Starting Up the IF 961-AIO Interface Submodule
Electrical Installation
You must connect the ground terminal (M and S
0/
S
1
) of the analog input/output
module with the ground terminal of the load power supply. Use a cable with a
cross-section of 1 mm
cross-section of 1 mm
2
for this purpose.
Unswitched Channels
You must short-circuit unswitched input channels. This achieves optimal noise
immunity for the analog module.
immunity for the analog module.
Leave unswitched output channels open.
13.7.7
Addressing
Addressing
The IF 961-AIO interface submodule is addressed with the M7-300/400-reserved
I/O address area (starting from C000
I/O address area (starting from C000
H
).
Addressing in the M7-300/400-Reserved I/O Address Area
The base address depends on the interface submodule slot in the expansion
module or the programmable module. See the descriptions “M7-300 Expansions”,
“M7-400 Expansions” or the description of the M7-400 programmable modules for
the slot-dependent base address of the interface submodule.
module or the programmable module. See the descriptions “M7-300 Expansions”,
“M7-400 Expansions” or the description of the M7-400 programmable modules for
the slot-dependent base address of the interface submodule.
The I/O address is the sum of the base address and the offset address.
The registers and their meanings and the offset addresses are described below.
Table 13-39
Offset Address Assignments for the IF 961-AIO Interface Submodule
Offset
Address
Function when
Reading
Function when
Writing
00
H
ADC data channel 0 (2
0
- 2
15
)
ADC data channel 0 (2
0
- 2
15
)
02
H
ADC data channel 1 (2
0
- 2
15
)
ADC data channel 1 (2
0
- 2
15
)
04
H
ADC data channel 2 (2
0
- 2
15
)
Reserved
06
H
ADC data channel 3 (2
0
- 2
15
)
Reserved
08
H
Indication of settings such as automatic
conversion, cycle time, interrupt enable
conversion, cycle time, interrupt enable
Setting of automatic conversion,
cycle time and interrupt enable
cycle time and interrupt enable
0A
H
Indication of channel number
Output of channel number
0C
H
Indication of end of conversion (EOC)
and voltage fault
and voltage fault
Start of analog-digital conversion
0E
H
Reserved
Interrupt acknowledgment