Mitsubishi Electronics A1SJ71AR23Q ユーザーズマニュアル
8
TROUBLESHOOTING
8.3 Checking Error with LEDs of Link Module on Faulty Station
8
- 14
1
O
V
ER
VI
E
W
2
S
YST
EM
CONF
IGURA
T
ION
3
S
P
E
C
IF
ICA
T
IONS
4
F
UNCT
IO
NS
5
PR
EP
ARA
T
O
R
Y
PR
O
C
E
DURES
BEF
ORE
OP
E
R
A
T
ION
6
L
INK DA
TA
SEN
D/
RE
C
E
IV
E
P
R
OCE
S
S
ING
A
N
D
P
R
OCE
S
S
ING
T
IME
7
P
R
OGRA
M
MING
8
TR
O
U
BL
ESHO
O
T
IN
G
8.3
Checking Error with LEDs of Link Module on Faulty Station
Any of the following LEDs will light up when an error occurs.
Table 8.1 ERROR LEDs
Indication
Name
Error-
detected
status
Description
CRC
CRC error
(Cyclic redundancy
check)
(Cyclic redundancy
check)
ON
Code check error of receive data
<Cause>
•Data-sending station was disconnected at the timing.
•Cable fault, noise, etc.
<Cause>
•Data-sending station was disconnected at the timing.
•Cable fault, noise, etc.
OVER
Overrun error
Received data were overwritten with another data received next due to delay in
loading.
<Cause> Hardware failure in receiving part of link module
loading.
<Cause> Hardware failure in receiving part of link module
AB.IF
Abort invalid frame error
"1" has been received consecutively more than stipulated times.
Receive data length is shorter than stipulated length.
<Cause>
•Data-sending station was disconnected at the timing.
•Monitoring time too short, cable fault, noise, etc.
Receive data length is shorter than stipulated length.
<Cause>
•Data-sending station was disconnected at the timing.
•Monitoring time too short, cable fault, noise, etc.
TIME
Time check error
Data link monitoring time is over.
<Cause> Monitoring time too short, cable fault, noise, etc.
<Cause> Monitoring time too short, cable fault, noise, etc.
DATA
Data check error
Data containing erroneous code have been received.
<Cause> Cable fault, noise, etc.
<Cause> Cable fault, noise, etc.
UNDER
Underrun error
Internal processing of send data is not executed constantly.
<Cause> Hardware failure in sending part of link module
<Cause> Hardware failure in sending part of link module
F.LOOP
Forward loop error
Forward loop line has an error.
Adjacent station was powered OFF.
<Cause> Forward loop cable disconnection, or incomplete cable connection
Adjacent station was powered OFF.
<Cause> Forward loop cable disconnection, or incomplete cable connection
R.LOOP
Reverse loop error
Reverse loop line has an error.
Adjacent station was powered OFF.
<Cause> Reverse loop cable disconnection, or incomplete cable connection
Adjacent station was powered OFF.
<Cause> Reverse loop cable disconnection, or incomplete cable connection