 - 4
Appendix 2 List of Special Registers (for Link)
 
APPENDICES
 * 1 Used for the MELSECNET data link system only.
144
H
324
D9252
Local station 
error status
Stores status data of 
station No.1 to No.16
•Stores station Nos. of faulty local stations except for the host 
station in the loop, into the corresponding bits in the special 
registers (for link) as shown below.
•Error detection is performed only for local stations other than the 
host station. Remote I/O station data are "0" and are not 
changed.
•Bits corresponding to the station Nos. of faulty local stations 
(except for host station) turn to "1". 
 (Example)  When local station No.12 is faulty, bit 11 in D9252 
turns to "1". 
By monitoring D9252, "2048 (800
H
)" is identified.
•Automatically turns to "0s" when faulty stations return to normal, 
or when data link returns to normal by loop line switching. 
145
H
325
D9253
Stores status data of 
station No.17 to No.32
146
H
326
D9254
 *1
Stores status data of 
station No.33 to No.48
147
H
327
D9255
 *1
Stores status data of 
station No.49 to No.64
Table App.2 List of special registers (for link) (Continued)
Buffer 
memory 
address
(Bit No.)
No.
Name
Description
Details
Hexad
ecimal
Decim
al
D9252
b15
b15 b14
b14 b13
b13 b12
b12 b11
b11 b10
b10 b9
b9 b8
b8 b7
b7 b6
b6 b5
b5 b4
b4 b3
b3 b2
b2 b1
b1 b0
b0
L16 L15 L14 L13 L12 L11 L10 L9 L8 L7 L6 L5 L4 L3 L2 L1
Device
Device
No.
No.
D9253 L32 L31 L30 L29 L28 L27 L26 L25 L24 L23 L22 L21 L20 L19 L18 L17
D9254 L48 L47 L46 L45 L44 L43 L42 L41 L40 L39 L38 L37 L36 L35 L34 L33
D9255 L64 L63 L62 L61 L60 L59 L58 L57 L56 L55 L54 L53 L52 L51 L50 L49
Bit No.
Bit No.