Mitsubishi Electronics A1SJ71AR23Q ユーザーズマニュアル

ページ / 158
5
 - 5
5.3 Part Names and Settings
 
5
PREPARATORY PROCEDURES BEFORE 
OPERATION
(1) Station No. setting
(a) MELSECNET data link system
Set "00" to the station No. of the master station, and set station No. 
(01
02
n(n
64) to slave stations starting from the one next to the master 
station.
POINT
(1) Set station No. from the smallest number in order.
(2) Do not skip any station No., since it has to be set in number order.
(3) Set station No. so as not to overlap with other station No. in the same tier.
6)
Connector (A1SJ71AR23Q)
Connects a coaxial cable.
7)
Terminal block 
(A1SJ71AT23BQ)
Connects a shielded twisted pair cable.
Figure 5.3 Station No. setting of MELSECNET data link system
Table 5.2 Part names and settings(Continued)
No.
Name
Description
IN R-SD
IN R-SD
IN F-RD
IN F-RD
OUT R-RD
OUT R-RD
OUT F-SD
OUT F-SD
Reverse loop send
Forward loop receive
Reverse loop receive
Forward loop send
Master station
for second tier
OUT
IN
Slave station
No.1
Station
No.01
OUT
IN
Master station
for third tier
Station
No.00
Station
No.00
OUT
IN
Slave station
No.2
Station
No.02
OUT
IN
Slave station
No.3
Station
No.03
OUT
IN
Slave station
No.64
Tertiary station
No.1
Tertiary station
No.2
Tertiary station
No.64
Station
No.64
Station
No.01
Station
No.02
Station
No.64
OUT
IN
OUT
IN
OUT
IN
OUT
IN
Forward
loop 
direction
Forward
loop 
direction