Motorola 3460 ユーザーズマニュアル

ページ / 188
3460 Fast’R
1-26
6.
Optionally, connect a remote alarm monitoring device to the 
AccessWay, to alert you to a fault in the DC output voltage.
a) Determine whether you want the alarm relay contacts 
open or closed when AccessWay output voltages are 
within normal operating range. The default setting is 
Normal Open.
b) Optionally, reverse this setting: at the front of the 
AccessWay, loosen a power module’s captive screws 
and pull the power module out of the AccessWay. Set 
the jumper to the Normal Closed position 
(Figure 1-12). Replace the power module in the 
AccessWay. Tighten the captive screws that secure it.
c) Connect two lengths of wire from the alarm monitor 
device terminals to the ALARM 1 terminals on the 
back of the AccessWay.
7.
If you disconnected the power terminal block from the rear of 
the AccessWay unit, replace it.
8.
Attach the cable clamp (Figure 1-13; provided with the 
AccessWay) to the wire bundle at the rear of the AccessWay. 
Leave a service loop of at least 8 cm between the clamp and the 
terminal block, and secure the clamp to the screw at the left of 
the terminal block.
Ensure that any strain is relieved from the cable terminals, and 
that the power terminal block is easily accessible should you 
need to remove it quickly in an emergency.
9.
Apply DC power to the AccessWay. 
Verify that the LEDs near the bottom of the power module(s) are 
lit. The LEDs indicate the presence of input voltage and the 
status of output voltage.
Connecting the AccessWay to DC Power Supply
 (continued)
Step
Action