Seagate Enterprise Capacity 3.5 HDD v4 SAS Product Manual, Rev. D
  30
  
6.4
Power dissipation
6TB models in 6Gb operation
To obtain operating power for typical random read operations, refer to the following I/O rate curve (see Figure 4). Locate the typical I/O rate 
for a drive in the system on the horizontal axis and read the corresponding +5 volt current, +12 volt current, and total watts on the vertical 
axis. To calculate BTUs per hour, multiply watts by 3.4123. 
Figure 4. 
6TB models (6Gb) DC current and power vs. input/output operations per second
6TB models in 12Gb operation
To obtain operating power for typical random read operations, refer to the following I/O rate curve (see Figure 5.). Locate the typical I/O 
rate for a drive in the system on the horizontal axis and read the corresponding +5 volt current, +12 volt current, and total watts on the 
vertical axis. To calculate BTUs per hour, multiply watts by 3.4123. 
Figure 5. 
6TB models (12Gb) DC current and power vs. input/output operations per second