4.2. 
Client Side Connection Descriptors 
Section Title 
Connections 
Column Title 
Function 
Legal Values 
Port 
Specify  which  port  the  device  is 
connected to the FieldServer 
P1-P8 (with 232/485 converter), R1-
R2
1
 
Protocol 
Specify protocol used 
InfraTox or Infra-Tox 
Baud* 
Specify baud rate 
19200 (Vendor limitation) 
Parity* 
Specify parity 
None (Vendor limitation) 
Data_Bits* 
Specify data bits 
8 (Vendor limitation) 
Stop_Bits* 
Specify stop bits 
Handshaking* 
Specify hardware handshaking 
None (Vendor limitation) 
 
Example 
 
//    Client Side Connections 
 
Connections 
Port, 
Protocol, 
Baud, 
Parity, 
 Stop_Bits 
 
R1, 
InfraTox, 
19200, 
None, 
 1 
 
 
4.3. 
Client Side Node Descriptors 
Section Title 
Nodes 
Column Title 
Function 
Legal Values 
Node_Name 
Provide name for node 
Up to 32 alphanumeric characters 
Node_ID 
Irrelevant  for  this  driver  as  long 
as  only  one  Node  is  connected. 
Otherwise  the  Node-ID  should  be 
the  number  of  points/sensors  for 
which  the  Zellweger  unit  is 
configured.    A  unique  Node_ID  is  
recommended  for  each  Zellweger 
Unit  as  it  may  be  useful  in 
exposing Node status information 
0-255 
Protocol 
Specify protocol used 
InfraTox, Infra-Tox. 
Port 
Specify at which port the device is 
connected to the FieldServer 
Ports  P1-P8  can  be  with  232/485 
converter. 
P1-P8  (with  232/485  converter), 
R1-R2
 
                                                 
1
 
Not  all  ports  shown  are  necessarily  supported  by  the  hardware.  Consult  the  appropriate  Instruction 
manual for details of the ports available on specific hardware.