Electric Radiant 
Ceiling Heat 
Panels
Installation & Maintenance Instructions
a
Read Carefully - These  instructions  are  written  to  help  you  prevent
difficulties that might arise during installation of heaters. Studying the
instructions  first  may  save  you  considerable  time  and  money  later.
Observe the following procedures and cut your installation time to a
minimum.
1. To prevent possible electrical shock, disconnect ALL power com-
ing to heater at main service panel before wiring or servicing.
2. All wiring must be in accordance with the National and Local 
Electrical Codes and the heater must be grounded as a precau-
tion against possible electrical shock.
3. Verify the power supply voltage coming to the heater matches the 
ratings printed on the heater nameplate before energizing.
4. This heater is NOT suitable for use in hazardous locations as 
described by the National Fire Protection Association (NFPA). 
DO NOT use in areas where gasoline, paint or other flammable 
liquids are used or stored. DO NOT use in wet areas or areas 
where corrosive agents are present, such as marine, green 
house, chemical storage, swimming pool, or areas of high 
humidity, unless special custom panels are used. Special custom 
panels may be available for certain environments. Contact manu-
facturer for details.
5. To prevent a possible injury or fire from falling panels, panels 
MUST be securely fastened to the building structure. 
When T-bar Mounted: The T-bar grid work frame must be 
secured to the building to provide adequate support for the pan-
els. Holes are provided in the sides of each panel for attachment 
of steel support wires for additional support of the panels where 
the T-bar grid work frame strength is questionable. Support wire 
must be steel and at least 18 gage (0.047 in. dia. / 0.119 cm. dia).
When Surface or Recess Mounted: The surface or recess mount-
ing frame accessory kits (Models ASF . . . or ARF . . . ) must be 
used. Kits must be sized to match heaters being used. Do not 
drill holes, drive nails, screws, etc., into or through panels. To do 
so may result in fire, electric shock, or permanent damage to 
heater. Surface or recess kits must be securely fastened to build-
ing structure using a minimum of four (4) 1/4 inch (.635 cm) diam-
eter screws or bolts.
6. To prevent possible fire due to the overheating of wiring, all field 
wiring coming to heating panels must be rated at least 90° C 
when junction box is allowed to lie on top of heating panel or is 
enclosed between heater and ceiling above. When thermal insu-
lation is used on top of heater, the junction box must be above 
the insulation.
7. Panels are intended for ceiling installation only. Do not install on 
walls, floor, etc. Painted (bottom) surface of panel is hot. Panels 
must be installed at least seven (7) feet off floor and should not 
be installed where panels can be easily contacted during use.
WARNING
SAVE THESE  INSTRUCTIONS
Dear Owner,
Congratulations! Thank you for purchasing this new heater manufactured by a division of Marley
Engineered Products. You have made a wise investment selecting the highest quality product in the heat-
ing industry. Please carefully read the installation and maintenance directions shown in this manual. You
should enjoy years of efficient heating comfort with this product from Marley Engineered Products . . .
the industry’s leader in design, manufacturing, quality, and service.
. . . The Employees of 
Marley Engineered Products
!
FILE #E21069
Marley  Engineered  Products  Radiant  Heating  Panels  are
designed  to  provide  comfort  by  warming  the  surfaces
below the heaters just as the sun warms surfaces through
radiant  energy.  This  heating  process  heats  objects  in  a
room without having to bring the room air temperature up
to the same level. These panels are ideal for spot heating
in  high  heat  loss  areas.  Panels  may  be  installed  side  by
side or individually above areas requiring additional heat. If
used as a sole source of heat, more heat will be felt while
standing directly under the panel. 
Although  the  heater  contains  thermal  insulation,  it  will
operate  more  efficiently  in  well  insulated  rooms.  Four  or
more  inches  of  insulation  above  an  exposed  ceiling  will
increase both comfort and economy. 
The heaters are intended to be controlled by a remote wall
mounted thermostat. The thermostat should be located in
the same room on a side wall. It should also be above 
five feet above the floor, but not directly under the heater.
GENERAL