 L676-1 Direct Vent Gas Fireplace
8
INST
ALLA
TION
INSTALLATION
This includes:
1)  Clocking the appliance to ensure the correct 
fi ring rate (rate noted on label 33,000 (NG)
    - High Altitude 32,000 (NG) Btu/h, 31,500 
(LP) Btu/h after burning appliance for 15 
minutes.
2)  If required, adjusting the primary air to ensure 
that the fl ame does not carbon.  First allow 
the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that 
causes sooting or carboning that results 
in damage is not the responsibility of the 
manufacturer.
MANUFACTURED 
MOBILE HOME 
ADDITIONAL 
REQUIREMENTS
1)  Ensure that structural members are not cut 
or weakened during installation.
2)  Ensure proper grounding using the #8 
ground lug provided. See "Wiring Diagram" 
section.
LOCATING YOUR 
GAS FIREPLACE
1)  When selecting a location for your fi replace, 
ensure that the clearances are met.
2)  The appliance must be installed on a fl at, 
solid, continuous surface (e.g. wood, metal, 
concrete). This may be the fl oor, or raised up 
on a platform to enhance its visual impact. 
The appliance must be installed on a metal 
or wood panel extending the full width and 
depth of the appliance.
3)  The L676-1 Direct Vent Gas Fireplace can 
be installed in a recessed position or framed 
out into the room as in A, B, C and D. See 
D) Corner
4)  This appliance is Listed for bedroom  
installations using the standard Remote 
(millivolt thermostat system). Some areas 
may have further requirements, check local 
codes before installation.
5)  The L676-1 Direct Vent Gas Fireplace 
is approved for alcove installations, see 
"Clearances" section for details.
6)  We  recommend that you plan your installation 
on paper using exact measurements for 
clearances and floor protection before 
actually installing this appliance. Have an 
authorized inspector, dealer, or installer 
review your plans before installation.
Note:   For vent terminations refer to 
"Exterior Vent  Termination Locations" 
HEATWAVE 
DUCT KIT 
The  HeatWave Air Duct Kit increases the 
effectiveness of your fi replace by dispersing warm 
air from the fi replace to remote locations in the 
same room or other rooms in your home.
Up to  two kits may be installed on the fi replace. 
Please Note: Only 1 HeatWave kit may be 
operated at one time. 
See HeatWave installation manual for complete 
details and clearances from side only.
Diagram 1
Diagram 1.
A)  Flat on Wall
B)  Flat on Wall Corner
C) Recessed 
into 
 Wall/Alcove
HEAT RELEASE KIT 
The Heat  Release Kit expels warm air from the 
fi replace to the outside of the building, allowing 
the fi replace to be operated with less heat entering 
the room. The kit may be used on either the left 
or right side.
See Heat Release installation manual for complete 
details and clearances from side only.
9)  Test Gas Pressure (Refer to "Gas Pipe Pres-
sure Testing" section).
10) Install standard and optional features.  Refer 
to the following sections: 
 a)  Brick 
Panels
 b)  Log 
Set
 
c) 
Remote Control - refer to "Matching  
 
Remote Handset & Control Box  
 
ID Code" section.
11) Final check.
Before leaving this unit with the customer, the 
installer must ensure that the appliance is fi ring 
correctly and operation fully explained to 
customer
.
The  HeatWave Duct Kit has different 
clearance and framing requirements, 
check the HeatWave manual for details.
FINISHED FLOOR
The maximum height that combustible fl oor can 
be brought above the base of the unit is 3".
IMPORTANT NOTE
Combustible material can only be installed to 
the bottom lip of the fi replace as shown below.  
The fi nished fl oor must not come in contact with 
the front face of the fi replace. Non-combustible 
material (see "Framing and Finishing" section) 
must act as a barrier between the front face and 
fi nished fl oor.