Rinnai REU-V2520FFU ユーザーズマニュアル

ページ / 48
Model #
Model #
Inlet Gas Pressure
Manifold Forced Low Fire
Manifold Forced High Fire
Inlet Gas Pressure
Manifold Forced Low Fire
Manifold Forced High Fire
REU-V2520FFU Series
REU-V2520FFUD Series
REU-V2532FFU Series
REU-V2532FFUD Series
REU-V2520FFU Series
REU-V2520FFUD Series
REU-V2532FFU Series
REU-V2532FFUD Series
6" - 10.5"
0.77"
3.7"
6" - 10.5"
0.77"
3.7"
10" - 13.5"
0.93"
4.2"
10" - 13.5"
0.93"
4.2"
Propane Gas Inlet and Manifold Gas Pressure by Model
Natural Gas Inlet and Manifold Gas Pressure by Model
NOTE: The pressure may be low due to too little flow, too high an incoming temperature, 
and/or undersized gas piping. Examine these areas before determining that the 
pressure needs to be adjusted. Contact Rinnai before adjusting manifold pressures at 
1-800-621-9419.  Failure to contact Rinnai, could void unit’s warranty.
Rinnai America
FF  Models
I N S TA L L E R ’ S  I N S TA L L AT I O N  I N S T R U C T I O N S
Testing
1)  Turn  on  the  gas  and  water. 
2)    Check  for  water  and  gas  leaks.  Use  soapy  water  to  test  for  gas  leaks. 
3)    Remove  pressure  test  point  screw,  attach  pressure  gauge  to  test  point. 
4)    Turn  Power  on. 
5)    Open  any  hot  water  tap  fully. 
6)    Check  test  point  or  supply  pressure  in  water  columns  per  inch. 
7)    If  it  is  determined  that  the  gas  pressure  needs  adjusting,  first  check  the  incoming 
pressure  at  the  test  point  on  the  gas  inlet.  If  it  is  correct  follow  the  adjusting 
procedure  contained  in  the  pouch  of  the  unit  EXACTLY.   
The  regulator  is  pre-set  at  the  factory,  it  should  not  need  resetting. 
8)    Turn  the  hot  water  off. Turn  the  power  off.  Remove  the  pressure  guage  and  replace 
the  test  point  screw.  Check  for  a  gas  leak  around  the  test  point  screw. 
9)  Replace  the  front  cover. 
10)  Turn  the  power  back  on. 
11)  Check  the  operation  of  the  unit.  Check  the  operation  of  each  of  the  remote 
controller(s).  Check  the  operation  of  the  Power  failure  protection  system. 
12)   Explain  the  proper  operation  of  the  Rinnai  Water  Heaters  to  the  customer.