Honeywell 62-2030-01 ユーザーズマニュアル

ページ / 28
STRYKER VAV USER GUIDE
15
62-2030—01
8. CONFIGURING THE CONTROL PARAMETERS
Use this page to set control parameters for an Stryker VAV device that are used to control the damper.
To set Control Parameters:
8.1 Fields
NOTE: The Pressurize, Depressurize, Night Purge, 
Emergency Purge and Morning Warmup values 
are configured as a percentage of maximum flow 
(pressure independent) or as percentage of 
damper position (Pressure dependant).
Step
Action
1
From the left pane of the 
VAV Configuration Wizard, select Control Parameters.
2
Enter information in the available fields.
3
Click 
Undo All to revert to the last saved settings.
4
Click 
Next to display the Schedule page.
5
Click 
Finish to save settings to station.
Table 9. Configuring the Control Parameter Fields.
Name
Definition
Maximum Flow Position
VAV Box Maximum damper position. Applies only to pressure dependent control mode or when a 
pressure independent airflow sensor fails.
Standby Flow Position
VAV Box minimum damper position used during standby mode. Applies only to pressure 
dependent control mode.
Minimum Flow Position
Zone terminal minimum cooling damper position during the occupied mode of operation. Applies 
only to pressure dependent control mode or when a pressure independent airflow sensor fails.
Reheat Flow Position
VAV Box maximum damper position in Reheat mode. The cooling air damper will be at this position 
at maximum reheat capacity.
Window Open
Window open damper position. When a window is open, air flow control is disabled and the flow 
damper is set to this position until the space temperature drops below the temperature set point.
Night Purge
Night purge damper setting.
Morning Warmup
Warmup damper setting.
Morning Warmup Type
Enables you to select the morning warmup type to be used when a 'MorningWarmup' command is 
received by the controller.
Mixed Air: The temperature control is turned off, and the damper is controlled as per the Warmup 
setting.
Warm Air with Reheat: Warm air is being supplied via the duct and the temperature control is 
reverse acting. ReHeat and peripheral may be turned on.
Warm Air without Reheat: Warm air is being supplied via the duct and the temperature control is 
reverse acting. ReHeat is disabled however peripheral heat may be used.
Pressurize
Damper setting to be used when a Pressurize Command is received over the network for smoke 
control operation.
Depressurize
Damper setting to be used when a De-Pressurize Command is received over the network for 
smoke control operation.
Emergency Purge
Damper setting to be used when an Emergency Purge Command is received over the network.
Unoccupied Minimum 
Flow Position
Minimum damper position to be used during unoccupied mode.