12.1 Fields
There are five categories of alarms:
Sensor Errors: These errors are generated for all the sensors 
that are connected to the onboard UI pins in the controller.
All such sensors are monitored by the controller for out-of-
range/invalid values.
Lon Network Communication Errors: These errors can 
occur for Lon NetworkVariable Inputs that are bound to other 
controllers when the source controller fails to send the 
data.The controller tracks and reports network communication 
errors for the following list of NVs when they are bound:
Control Alarms: These are application specific alarms tracked and reported by the controller.
Name
Definition
Error
Displays the name of the error.
Type of error
Displays the type of the error. Errors could be one of the following types:
1. Sensor Error
2. Lon Network Communication Error
3. Control Error
4. Sylkbus communication error
5. Node disabled error
For more information, see the descriptions below this table.
Details
This is a description of the error.
Enable Auto Alarm 
Refresh
When the 
Auto Refresh checkbox is selected, the alarms view/data refreshes automatically every 
30 seconds.
Refresh
Click 
Refresh to refresh the error list manually and see the current errors.
Network Variable
nviBypass
nviApplicMode
nviDlcShed
nviDschrgAirTemp
nviFan
nviFlowOffset
nviFlowTrack
nviFree1Dig
nviFree1Mod
nviOccCmd
nviOdTemp
nviSetPoint
nviShare
nviSpaceCO2
nviSpaceHum
nviSpaceTemp
nviSupplyTemp
nviTodEvent
nviWindow
nviFlowOverride
 nviSupplyTemp
nviMonDig
nviManOcc
nviEmergCmd
nviSetPointOvr
nviSetPtOffset
nviMonSensor
Network Variable
Alarm Name
Alarm Description
Frost
The space temperature detected is below the freeze protect limit.
Invalid Set Point
One of the temperature set points is not in the valid range.
Flow Override
The air flow control loop has been overridden.
Emergency Override
An emergency override command has been received from the network.
Fan Override
The fan is in the manual override state.
Reheat or Peripheral Heat 
Override
The reheat or peripheral heat outputs are overridden.
IAQ alarm
The indoor air quality sensor has detected that the indoor air quality is poorer than the 
desired standard.
Occupied Space Temperature The space temperature detected is out of range of the configured limits.
Low Air Flow
Air flow detected is too low to perform the flow control operation.