Introduction
3
Figure 2
Typical system configuration—indoor unit and outdoor condenser and field piping
Lee-Temp Receiver
Fan Speed and VFD
Lee-Temp
Service
Valve
External 
Equalizer
Liquid
Sensing
Bulb
Inverted trap on discharge  & liquid 
lines to extend above base of coil 
by a minimum of 7-1/2” (190mm).
Field-installed relief valve (s) required
for 50 Hz EU CE units rated maximum 
480 PSIG (33 Bar).
* Isolation
  valve
* Traps every
   25ft (7.6m)
   of rise
Fusible
Plug
Suction
Hot Gas Discharge
Liquid Return
Filter Dryer
Sight Glass
Solenoid
Valve
Expansion
Valve
DPN000798
Rev. 2
Condenser Coil
(Fan Speed
and VFD)
Condenser Coil
(Lee-Temp)
Evaporator Coil
Compressor
Service
Valve
Check
Valve
* Isolation
   valve
28-42kW Digital Solenoid Valve
53-70kW Digital 
Solenoid Valve
Factory Refrigerant Piping
Field Refrigerant  Piping
Service/Schrader  (Access) Connection No Valve Core
Note: Schematic representation shown . Do not use for specific connection locations .
Two refrigeration circuits provided . Single refrigeration circuit shown for clarity .
Service/Schrader  (Access) Connection With Valve Core
Liquid Return
Hot Gas 
Discharge
Head Pressure 
Control Valve
Check
Valve
Relief
Valve
Service
Valve
Components are not supplied by 
Liebert, but are recommended 
for proper circuit operation and 
maintenance.
*
Pitch horizontal hot gas piping
1/2" per 10 ft. (42mm per 10m) 
in direction of refrigerant/oil flow.