Mitsubishi Electronics Q13UD(E)HCPU ユーザーズマニュアル

ページ / 212
1
SAFETY PRECAUTIONS
(Read these precautions before using this product.)
Before using this product, please read this manual and the relevant manuals carefully and pay full attention 
to safety to handle the product correctly.
In this manual, the safety precautions are classified into two levels: "
WARNING" and "
CAUTION".
Under some circumstances, failure to observe the precautions given under "
CAUTION" may lead to 
serious consequences.
Observe the precautions of both levels because they are important for personal and system safety.
Make sure that the end users read this manual and then keep the manual in a safe place for future 
reference.
[Design Precautions]
 WARNING
● Configure safety circuits external to the programmable controller to ensure that the entire system 
operates safely even when a fault occurs in the external power supply or the programmable controller. 
Failure to do so may result in an accident due to an incorrect output or malfunction.
(1) Configure external safety circuits, such as an emergency stop circuit, protection circuit, and 
protective interlock circuit for forward/reverse operation or upper/lower limit positioning.
(2) The programmable controller stops its operation upon detection of the following status, and the 
output status of the system will be as shown below.
All outputs may turn on when an error occurs in the part, such as I/O control part, where the 
programmable controller CPU cannot detect any error. To ensure safety operation in such a case, 
provide a safety mechanism or a fail-safe circuit external to the programmable controller. For a 
fail-safe circuit example, refer to the QCPU User's Manual (Hardware Design, Maintenance and 
Inspection).
(3) Outputs may remain on or off due to a failure of an output module relay or transistor. Configure an 
external circuit for monitoring output signals that could cause a serious accident.
WARNING
CAUTION
Indicates that incorrect handling may cause hazardous conditions,
resulting in death or severe injury. 
Indicates that incorrect handling may cause hazardous conditions,  
resulting in minor or moderate injury or property damage.
Overcurrent or overvoltage protection of
the power supply module is activated.
The CPU module detects an error such as a
watchdog timer error by the self-diagnostic function.
All outputs are turned off
All outputs are turned off
All outputs are turned off
All outputs are held or turned off
according to the parameter setting.
Q series module
AnS/A series module