Maintenance 
9.2 Fail‐Safe Operation 
The Fail‐Safe system is  designed  to alert the operator and provide a 
safe  output  in  case  of  any  system  failure.  The  sensor  is  designed  to 
shutdown the process in the event of a set‐up error, system error, or a 
failure in the sensor electronics. 
The  Fail‐Safe  circuit  should  never  be  relied  on 
exclusively  to  protect  critical  processes.  Other  safety 
devices should also be used to supplement this function! 
When  an  error  or  failure  does  occur,  the  display  indicates  the 
possible  failure  area,  and  the  output  circuits  automatically  adjust  to 
their preset levels, see the following tables. 
Error Codes for the Outputs 
Symptom 
mV 
0 to 20 mA 
4 to 20 mA 
TC-K 
TC-J 
Temperature over 
range 
5 V 
21 mA 
21 mA 
Temperature under 
range 
0 V 
2.5 mA 
0 mA 
Defect of the internal 
head ambient 
temperature probe 
5 V 
21 mA 
21 mA 
> 1200°C 
(2192 °F) 
> 1200°C 
(2192 °F) 
Table 7: Error Codes (Outputs) 