Sterling 882.000254.00 ユーザーズマニュアル

ページ / 91
7/50D Plus or 7/50D Controller 
Chapter 6:  Configurable Settings 
75 
Name Description 
Options 
Default 
Partial convey 
When this option is enabled, the controller 
issues a “partial convey” alarm if it has 
repeatedly attempted to convey material to the 
station, and material has moved from the station 
into the receiver, but the volume-fill proximity 
sensor has never signaled that the station is full. 
(The number of attempts is controlled by the 
next setting.) 
For a volume-fill station, this option should 
usually be enabled. At times, you may wish to 
disable it during operation as a stopgap 
measure for dealing with an alarm. For a time-fill 
station, disable this option. 
disabled, 
enabled 
disabled 
Alarm Options 
# attempts B4 alarm 
Number of attempts before alarm: the number of 
times the controller will attempt to convey 
material to a station before it issues a “partial 
convey” alarm. 
The setting for this option depends on the same 
considerations as those given above for number 
of attempts before a “no convey” alarm. 
1–99 3 
Local alarm 
When this option is enabled, the controller turns 
on the local alarm light for any alarm at this 
specific station. 
Enable this option if and only if your facility has 
installed a local alarm light for this station. 
disabled, 
enabled 
disabled 
Miscellaneous Options 
Receiver low level 
When this option is enabled, the controller 
issues a “receiver level” alarm if material in the 
receiver drains below the level of the receiver’s 
low-level sensor. 
Enable this option if and only if your facility has 
installed a low-level sensor for this station’s 
receiver. At times, you may wish to disable it 
during operation as a stopgap measure for 
dealing with an alarm. 
disabled, 
enabled 
disabled 
Blow Back Options  (Only available on 7/50D Plus systems) 
Blow back 
When this option is enabled, the controller 
periodically sends compressed air backward 
through the station’s air filter to dislodge 
accumulated dust and debris. 
Enable this option if and only if the station has 
the equipment for compressed-air filter cleaning.
disabled, 
enabled 
disabled 
Every n loads 
Number of conveying cycles between filter 
cleanings. 
Adjust this setting based on experience. The 
more dust and debris in your material line, the 
smaller this number needs to be. 
1–99 5 
# pulses 
Number of pulses of compressed air sent 
through the station’s filter during cleaning. 
If blow-back is not working as desired, the 
service department may ask you to change this 
setting.  
1–99 5