Mitsubishi Electronics MELSEC Q series MELSEC L series ユーザーズマニュアル
5-146
5.4 Network Dedicated Instruction
5.4.8 READ instruction
5.4.8 READ instruction
J_READ, G_READ
5.4.8
READ instruction
J_READ, G_READ
*1 :
Local devices and file registers per program cannot be used as setting data.
*2 :
Only CC-Link IE Field Network
When the target station is LCPU, Universal model QCPU, or Basic model QCPU, the digit specification
of the bit device can be used (example: K4M16).
The digit specification of the bit device can be used when the following conditions are met.
When the target station is LCPU, Universal model QCPU, or Basic model QCPU, the digit specification
of the bit device can be used (example: K4M16).
The digit specification of the bit device can be used when the following conditions are met.
• The device number is a multiple of 16 (10
H
).
• The digit specification is 4 points (K4).
Function
This instruction reads data from a word device of another station.
J(P)_READ
G(P)_READ
G(P)_READ
P: Executing condition
:
indicates any of the following
instructions.
J_READ
JP_READ
G_READ
GP_READ
Input argument
EN:
Executing condition
:Bit
Jn*:
Network number of the host station (1 to 239, 254)
254: Network specified in
254: Network specified in
"
Valid module during other station
access
"
:ANY16
Un*:
Start I/O number of the module
(00 to FE: Higher two digits when expressing the I/O number in
three digits)
(00 to FE: Higher two digits when expressing the I/O number in
three digits)
:ANY16
s1:
Variable that stores control data
:Array of ANY16 [0..17]
s2:
Start number of the target station's device from which data are
read
read
:ANY
Output argument
ENO:
Execution result
:Bit
d1:
Start number of the host station's device that stores read data :ANY16
d2:
Variable that turns ON upon completion of the instruction
d2[1] also turns ON at the time of error completion.
d2[1] also turns ON at the time of error completion.
:Array of bit [0..1]
Setting
data
*1
Internal device
R, ZR
J
\
U
\G
Zn
Constant Others
Bit
Word
Bit
Word
*2
CC IE F
CC IE C
NET/H
Ether
Structured ladder/FBD
EN
ENO
Jn*
d1
d2
s1
s2
EN
ENO
Un*
d1
d2
s1
s2
ST
(EN, Jn*, s1, s2, d1, d2);
ENO:=
(EN, Un*, s1, s2, d1, d2);
ENO:=
J_READ
G_READ
J_READ
G_READ
s1
s2
d1