Mitsubishi Electronics MELSEC Q series MELSEC L series ユーザーズマニュアル

ページ / 412
5.4 Network Dedicated Instruction
5.4.30 ERRCLR instruction
5-237
ZP_ERRCLR
5
MODULE DEDICA
TED 
INSTRU
CTI
O
N
Z
P
_ERRCLR
5.4.30  
ERRCLR instruction
ZP_ERRCLR
*1: Local devices and file registers per program cannot be used as setting data.
Function
This instruction turns OFF the LED on Ethernet module and clears error information stored in the 
buffer memory.
ZP_ERRCLR
Executing condition
:
 indicates the following instruction.
ZP_ERRCLR
Input argument
EN:
Executing condition
:Bit
Un*:
Start I/O number of the module
(00 to FE: Higher two digits when expressing the I/O number in 
three digits)
:String
s:
Variable that stores control data
:Array of ANY16 [0..7]
Output argument
ENO:
Execution result
:Bit
d:
Variable that turns ON upon completion of the instruction
d[1] also turns ON at the time of error completion.
:Array of bit [0..1]
Setting
data 
*1
Internal device
R, ZR
J
\
U
\G
Zn
Constant Others
Bit
Word
Bit
Word
Ether
ZP_ERRCLR
EN
ENO
Un*
d
s
ZP_ERRCLR
(EN, Un*, s, d);
ENO:=
Structured ladder/FBD
ST
s
d