9 - 107 
MELSEC-Q
 
9   MAJOR POSITIONING CONTROL 
 
(4)  If the value set in "
Da.6
 Positioning address/movement amount" is outside 
the software stroke limit (
Pr.12
,
Pr.13
) setting range, an error "Software 
stroke limit +, - (error code: 507 or 508)" will occur at the positioning start, and 
the operation will not start. 
 
(5)  An error (error code: 507 or 508) will occur if the new current value is outside 
the software stroke limit range. 
 
(6)  The new current value using the positioning data (No.1 to 600) cannot be 
changed, if "0: Positioning control is not executed" is set in "
 Pr.55
 Operation 
setting for incompletion of OPR" and "OPR request flag" ON. A warning 
"Operation setting for incompletion of OPR at positioning start error" (error 
code: 547) will occur. 
 
 Positioning data setting examples 
The following table shows the setting examples when " current value changing" is 
set in the positioning data No. 1 of axis 1. 
 
Setting item 
Setting example 
Setting details 
 Da.1  
Operation 
pattern 
Positioning complete 
Set "Positioning complete" assuming that 
the next positioning data will be executed. 
("Continuous path control" cannot be set by  
current value change.) 
 Da.2  
Control 
system 
Current value changing 
Set the current value changing. 
 Da.3  
Acceleration 
time No. 
– 
Setting not required (Setting value is 
ignored.) 
 Da.4  
Deceleration 
time No. 
– 
Setting not required (Setting value is 
ignored.) 
 Da.5  
Axis to be 
interpolated 
– 
Setting not required (Setting value is 
ignored.) 
 Da.6  
Positioning 
address/ 
movement 
amount 
10000.0 m 
Set the address to which address change is 
desired. (Assuming that the "
Pr.1
 Unit 
setting" is set to "mm".) 
 Da.7  
Arc address 
– 
Setting not required (Setting value is 
ignored.) 
 Da.8  
Command 
speed 
– 
Setting not required (Setting value is 
ignored.) 
 Da.9  
Dwell time 
– 
Setting not required (Setting value is 
ignored.) 
Axis 1 
positioning 
data No. 1 
 Da.10   
M code 
10 
Set this when other sub operation 
commands are issued in combination with 
the No. 1 positioning data. 
 
 Refer to Section 5.3 "List of positioning data" for information on the setting details.