12 - 41 
MELSEC-Q
 
12   CONTROL SUB FUNCTIONS 
 
[3]   Setting the forced stop 
To use the "Forced stop function", set the following data using a PLC program. 
The set details are validated at the rising edge (OFF   ON) of the PLC READY 
signal (Y0). 
 
Setting item 
Setting 
value 
Setting details 
Buffer memory address 
 Pr.82 
 
Forced stop valid/ invalid 
selection 
 
Set the forced stop function. 
0 :  Valid    (Forced stop is used) 
1 :  Invalid    (Forced stop is not used) 
35 
 
 Refer to Section 5.2.3 "Detailed parameters 1" for details on the setting details. 
 
[4]   How to check the forced stop 
To use the states (ON/OFF) of forced stop input, set the parameters shown in the 
following table. 
 
Setting item 
Setting 
value 
Setting details 
Buffer memory address 
Md.50
 Forced stop input 
 
Stores the states (ON/OFF) of forced stop input. 
0 :  Forced stop input ON (Forced stop) 
1 :  Forced stop input OFF (Forced stop release) 
1431 
 
 Refer to Section 5.6.1 "System monitor data" for details on the setting details. 
 
[5]   Precautions during control 
(1)  After the "Forced stop input" is released, the servo ON/OFF is valid for the 
status of all axis servo ON (Y1). 
(2)  If the setting is other than 0 and 1, "Forced stop valid/invalid setting error" 
(error code: 937) occurs. 
(3) The 
"
Md.50
Forced stop input" is stored "1" by setting "
 Pr.82
Forced stop 
valid/invalid selection" to invalid. 
(4)  When the "Forced stop input" is turned ON during operation, the "Servo 
READY signal OFF during operation error (error code: 102)" will not occur.