Omron C200HW-ZW3AT2-E-V2 ユーザーズマニュアル

ページ / 182
4-2
Section
Starting Data Links
38
4-1
Starting the Network for the First Time
1, 2, 3...
1. System Setup
Set up the Controller Link Support Software operating environment and the
PCs to be connected.
This step does not necessarily need to be performed first, but it does need to
be performed before transferring data between the Controller Link Support
Software and nodes, printing data, or executing the functions on the
 
Mainte-
nance Menu.
Main Item Selection
Main Menu 
 I:System setup
2. Broadcast Test
If necessary, conduct a communications test for the entire network to check
for any communications problems.
Main Item Selection
Main Menu 
 D:Broadcast test
3. Echoback Test
If necessary, conduct a communications test (stricter than the broadcast
test) for each node and make sure that the Controller Link Support Software
can communicate normally with each node.
Main Item Selection
Main Menu 
 N:Echoback test
4. PC IDs (This step is optional.)
Assign a PC ID to each node to facilitate node management and Controller
Link Support Software operations.
Main Item Selection
Main Menu 
 W:Edit PC ID
4-2
Starting Data Links
4-2-1 Manually Set Data Links
1, 2, 3...
1. Setting Device Information
Specify the model of each node on the Controller Link Network. This in-
formation is used to perform word address validity checks when data link
tables are created or edited.
Main Item Selection
Main Menu 
 L:Data Link 
 Data Link submenu (F2) 
 I:Device Info set
2. Creating Data Link Tables
Data link tables are required for manually set data links.
Main Item Selection
Main Menu 
 L:Data Link
3. Checking Data Link Tables
Check the created data link tables for errors or inconsistencies.
Main Item Selection
Main Menu 
 L:Data Link 
 Data Link submenu (F2) 
 K:Check table
4. Transferring the Data Link Tables
Transfer the created data link tables to the nodes.
Main Item Selection
Main Menu 
 L:Data Link 
 Data Link submenu (F2) 
 T:Transfer table
 W:Computer
Controller Link