2 Wiring and Connection
MITSUBISHI CNC
2 - 4
2-2 Main circuit terminal block/control circuit connector
2-2-1 Names and applications of main circuit terminal block signals and control circuit 
connectors
The following table shows the details for each terminal block signal.
Name
Signal name
Description
L1 . L2 . L3
Main circuit power 
supply
Main circuit power supply input terminal
Connect a 3-phase 200VAC (50Hz) or 200 to 230VAC (60Hz).
(N . P1 . P2)
Not used
Not used (Short between P1 and P2.)
P.C.D
Regenerative 
resistor
Regenerative resistor connection terminal
When using the built-in regenerative resistor, short between P and D.
P to D is wired at shipment.
When using the external option regenerative resistor, disconnect the wire between P and 
D, and wire the external option regenerative resistor between P and C.
L11  L21
Control circuit power 
supply
Control circuit power supply input terminal
Connect a single-phase 200VAC (50Hz) or 200 to 230VAC (60Hz).
U . V . W
Motor output
Servo/spindle motor power output terminal (3-phase AC output)
The servo/spindle motor power terminal (U, V, W) is connected.
Protective grounding 
(PE)
Grounding terminal
The servomotor/spindle motor grounding terminal is connected and grounded.
1. When sharing a circuit protector for several drive units, of a short-circuit fault occurs in a small 
capacity unit, the circuit protector could trip. This can be hazardous, so do not share the circuit 
protector.
2. Be sure to use the circuit protector of proper capacity for each drive unit.