Mitsubishi Electronics AJ61BT11 ユーザーズマニュアル

ページ / 294
 
 
 
8 - 18 
8   PROGRAMMING 
MELSEC-QnA 
 
Table 8.2 Link special register list (continued) 
 
Availability  
(  : available,  
   : not available ) 
Online 
Number Name 
Description 
Master 
station 
Local 
station
Offline
SW0049 
(649
H
Temporary error invalid 
station request result 
Stores the execution results of the temporary error invalid station 
request specification by SB0004. 
0 : 
Normal 
Other than 0  : Stores error code (Refer to Section 13.3.) 
 
 
 
SW004B 
(64B
H
Temporary error invalid 
station cancelling request 
result 
Stores the execution results of the temporary error invalid station 
cancelling request specification by SB0005. 
0 : 
Normal 
Other than 0  : Stores error code (Refer to Section 13.3.) 
 
 
 
SW004D  
(64D
H
Line test request result 
Stores the execution results of the line test request specification by 
SB0008. 
0 : 
Normal 
Other than 0  : Stores error code (Refer to Section 13.3.) 
 
 
 
SW004F  
(64F
H
Parameter setting test 
request result 
Stores the execution results of the parameter setting test request by 
SB0009. 
0 : 
Normal 
Other than 0  : Stores error code 
 
 
 
SW0060 
(660
H
Mode setting switch status 
Stores the setting status of the mode setting switch. 
0: Online (remote net mode) 
1: Online (remote I/O net mode) 
2: Offline 
3: Line test 1 
4: Line test 2 
5: Parameter verification test 
6: Hardware test 
 
 
 
SW0061 
(661
H
Station number setting 
switch status 
Stores the station number setting switch's setting status. 
: Master station 
1 to 64  : Local station 
 
 
 
SW0062 
(662
H
Condition setting switch 
status 
The setting status of the condition setting switch (DIP switch) is 
stored. 
0: OFF 
1: ON 
0
0
to
b15
b8 b7 b6 b5 b4 b3 b2 b1 b0
SW1
SW2
SW3
SW4
SW5
SW6
SW7
SW8
 
 
 
 
SW0064  
(664
H
No. of retries setting 
information 
Stores the number of retries setting information when responding to 
an error. 
1 to 7 (times) 
 
 
 
SW0065  
(664
H
No. of automatic return 
stations information 
Stores the number of automatic return stations setting information 
during one link scan. 
1 to 10 (modules) 
 
 
 
SW0066  
(666
H
Delay timer information 
Stores the delay time setting information. 
 
 
 
SW0067 
(667
H
Parameter information 
The parameter information area to be used is stored. 
1: Buffer memory (data link startup by Yn6) 
2: E
2
PROM (data link startup by Yn8) 
 
 
 
SW0068 
(668
H
Host parameter status 
Parameter setting status is stored. 
0 : 
Normal 
Other than 0  : Stores error code (Refer to Section 13.3.) 
 
 
 
  : Link special relay added to the function version B or later