Mitsubishi Electronics AJ61BT11 ユーザーズマニュアル
APPX - 3
MELSEC-QnA
APPENDICES
Appendix 2 Parameter Setting Sheet
Item Setting
range
Buffer memory
address
Remark
Default value Setting value
Number of linked
modules
modules
1 to 64
1
H
– 64
Number of retries
1 to 7
2
H
– 3
Number of automatic
return modules
return modules
1 to 10
3
H
– 1
Standby master station
specification
specification
0 to 63
(0: No specification)
(0: No specification)
4
H
– 0
Operation when CPU
down
down
0: stop
1: continue
1: continue
6
H
–
0
(stop)
Delay time setting
Set 0.
8
H
– 0
10
H
Station No. 16 to 1
0000
H
11
H
Station No. 32 to 17
0000
H
12
H
Station No. 48 to 33
0000
H
Reserved station
specification
specification
Turn on the corresponding
bit for station to reserve.
bit for station to reserve.
13
H
Station No. 64 to 49
0000
H
14
H
Station No. 16 to 1
0000
H
15
H
Station No. 32 to 17
0000
H
16
H
Station No. 48 to 33
0000
H
Invalid station
specification
specification
Turn on the corresponding
bit for station to invalidate.
bit for station to invalidate.
17
H
Station No. 64 to 49
0000
H
20
H
1st
module
0101
H
21
H
2nd
module
0102
H
22
H
3rd
module
0103
H
23
H
4th
module
0104
H
24
H
5th
module
0105
H
25
H
6th
module
0106
H
26
H
7th
module
0107
H
27
H
8th
module
0108
H
28
H
9th
module
0109
H
29
H
10th
module
010A
H
2A
H
11th
module
010B
H
2B
H
12th
module
010C
H
2C
H
13th
module
010D
H
2D
H
14th
module
010E
H
2E
H
15th
module
010F
H
2F
H
16th
module
0110
H
30
H
17th
module
0111
H
31
H
18th
module
0112
H
32
H
19th
module
0113
H
33
H
20th
module
0114
H
34
H
21st
module
0115
H
35
H
22nd
module
0116
H
36
H
23rd
module
0117
H
37
H
24th
module
0118
H
38
H
25th
module
0119
H
39
H
26th
module
011A
H
3A
H
27th
module
011B
H
Station information
b15 to b12 (station type)
0: remote I/O station
1: remote device station
2: intelligent device station,
0: remote I/O station
1: remote device station
2: intelligent device station,
local station
b11 to b8 (number of
occupied stations)
1: occupies one station
2: occupies two stations
3: occupies three stations
4: occupies four stations
b7 to b0 (station number)
01
H
to 40
H
(1 to 64)
3B
H
28th
module
011C
H