Mitsubishi Electronics AJ65bt-r2 ユーザーズマニュアル

ページ / 264
7 - 27
MELSEC-A
7   USING FRAMES WHEN EXCHANGING DATA
1)   Designating to the buffer memory
The RX/RY/RW reference special characters are written directly after
the designating character.
(Example) To 123
H
 for RW, write as follows in the buffer memory.
FF
H
DA
H
123
H
42
H
DA
H
01
H
41
H
FF
H
23
H
(H)
(L)
FF
H
23
H
45
H
42
H
DA
H
01
H
(H)
(L)
RW designation: 123
H
or
Previous designation data
Previous designation data
Previous designation data
2)   Designating RX/RY/RW
The RX/RY/RW designation in the 3rd and 4th bytes of the RX/RY/RW
reference special characters are designated as follow.
b15
b0
b13 b12 b11
0
0/1
0
1
RY
RX
RWw
RWr
Device No. 
Device type
For RX/RY 
designation
For RW 
designation
POINT
During frame transmission or monitor transmission, if the results of analyzing
and developing the user registration frame containing a special character
exceeds 2048 bytes, the "transmission data size over error (BB92
H
) will occur.
When using a special character (special character code C0
H
, C1
H
, D0
H
) to
designate the registration frame No., if the same registration frame No. is
designated in that designated registration frame, a special character cannot be
contained.
      
FF
H
D0
H
The special character No. cannot contain the C0
H
,
C1
H
 or D0
H
 character in the registration frame indicated 
by RW designated with the RX/RY and RW designation.
For RX/RY, RW designation