Mitsubishi Electronics AJ65bt-r2 ユーザーズマニュアル

ページ / 264
5 - 14
MELSEC-A
5   PRELIMINARY INFORMATION
(4)   Program
Refer to section 5.1 for details on the program conditions.
R2 normal
Set initial data
read request
Reset initial data
read request
Initial data read
complete
Set initialization data
write complete flag
Set initialization request
Reset initialization request
Initialization complete
Reading of remote input (RX) (Refer to section 5.3 (2).)
Master station initialization (parameter setting, data link setting) (Refer to section 5.4.) 
Confirmation of R2 data link status (Refer to section 5.3 (3).)
Write initialization data to automatic update buffer (Refer to section 5.6.)
Transmission of data to external device (Refer to section 6.3.1.)
Receiption of data from external device (Refer to section 6.3.2.)
R2 error processing (Refer to section 5.3 (7).)
Writing of remote output (RY) (Refer to section 5.3 (8).)
Set the error 
occurrence flag 
POINT
Create the following interlock circuit so that the initialization request is made after all
request signals (RY) are turned OFF.
SET  (RYn4)
Error reset 
request 
(RY(n+1)A)
Initialization 
command
Transmis-
sion request 
(RYn0)
Transmis-
sion cancel
request
(RYn1)
Reception 
read output 
complete 
(RYn2)
Forced 
reception 
complete 
request 
(RYn3)
OS 
reception
buffer clear
request
(RYn6)
EEPROM 
function 
request 
(RYn7)
Initialization
request 
(RY(n+1)9)
If initialization is carried out while RX or RY is ON, the current process will be canceled.
Start initialization after turning all RY, other than RYn4, OFF.