Honeywell 301C ユーザーズマニュアル

ページ / 107
Honeywell 301C User Manual 
Starting and Stopping Event Logging 
 
The Acquisition menu offers an event logging option.  Event Logging 
records controller transactions, events, Tx and alarm flags and relay 
status.   
 
When “Start Event logging” appears on the display, it  indicates that 
the acquisition, or logging, mode is inactive.  When “Stop Event 
logging” appears, it indicates that Event data is being logged.   
 
Press the Enter keypad button to stop or start Event logging. 
 
When Event data is logged, the system creates a file named 
evyymmdd.log.  The record includes the date, time and the event.  
Here is a sample of what an Event log looks like: 
 
       
 
The first column of the Event log displays the date (yyyy-mm-dd) and 
time (hh:mm:ss) of the log. Column A displays the date and time of the 
log.  In this example, the event’s “Delay mode” was set to one minute 
intervals. 
 
The system logs the following types of events:  
 
•   Event Log 
•   Event status changed  
•   Alarm A, B, C, Fault, and X status changed   
 
Note: New log files are created when the existing files reach 32 000 
lines or at the start of a new week (0h00 Sunday) 
2004-01-23 17:54:25: Event logging enable
2004-01-23 17:55:25: Event logging enabled
2004-01-23 19:05:47; Simulation sequence activated
2004-01-23 19:05:48; Tx 6 communication no more in fault
2004-01-23 19:05:48; Tx 8 communication no more in fault