Honeywell 301C ユーザーズマニュアル

ページ / 107
Honeywell 301C User Manual 
IAQPoint2 
  
77 
 
Data Type
Required
1
Storage 
Type
2
BACnet 
Writeable?
Value
object_identifier
R
C
N
Modbus address * 256 + 1.  For example an 
IAQPoint2 at Modbus address 005 will 
appear as 1281 or 0x0501.
object_type
enumerated
R
C
N
analog_input (0)
event_state
enumerated
R
R
N
if gas sensor fault Fault (1),
else normal (0)
object_name
character string
R
N
N
"IAQPoint CO2   AdXXX .CO2" where XXX  is 
the Modbus address.
out_of_service
boolean
R
R
N
FALSE
present_value
real
R
R
N
Gas reading
if CO2 fitted, 0 to 5000
if VOC fitted, 0 to 100
IA
QP
oi
nt
 C
O
2
reliability
enumerated
O
R
N
As appropriate reports
no_fault_detected (0) or
no_sensor (1) or
unreliable other (7)
Fault is detected within 60 seconds
status_flags
in_alarm
boolean
R
R
N
if faulty "true" (1)
else "false" (0)
fault
boolean
R
R
N
if faulty "true" (1)
else "false" (0)
overridden
boolean
R
R
N
"false" (0)
out_of_service boolean
R
R
N
"false" (0)
units
enumerated
R
N
N
if CO2 fitted, ppm (96)
if VOC fitted, %      (98)
object_identifier 
R
C
N
Sensor number * 256 + 1.  Sensor number 
for temperature is Modbus address + 1.  For 
example an IAQPoint2 at Modbus address 
005 will appear as 1537 or 0x0601.
object_type
enumerated
R
C
N
analog_input (0)
event_state 
enumerated
R
R
N
if temp sensor fault, fault (1),
else normal (0)
object_name
character string
R
N
N
"IAQPoint ToC   AdXXX .ToC" where XXX  is 
the Modbus address plus one.
out_of_service
boolean
R
R
N
FALSE
present_value
real
R
R
N
Temperature reading in Celcius, regardless 
of IAQPoint2 configuration.
reliability
enumerated
O
R
N
As appropriate reports
no_fault_detected (0) or
no_sensor (1) or
unreliable other (7)
Fault is detected within 60 seconds
status_flags
in_alarm
boolean
R
R
N
if not purchased or faulty "true" (1)
else "false" (0)
fault
boolean
R
R
N
if not purchased or faulty "true" (1)
else "false" (0)
overridden
boolean
R
C
N
False (0)
out_of_service boolean
R
R
N
"false" (0)
units
enumerated
R
N
N
Celcisus  (62)
Notes
1  --  'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 --  'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM.