Honeywell 301C ユーザーズマニュアル

ページ / 107
Honeywell 301C User Manual 
E³Point continued
  
 
82 
 
Group
Property
Data Type
Required
1
Storage 
Type
2
BACnet 
Writeable?
Value
object_identifier
R
N
N
Modbus address * 256 + 2.  For example an 
E3Point at Modbus address 000 will appear 
as 2306 or 0x0902.
object_type
enumerated
R
C
N
analog_value (2)
event_state
enumerated
R
C
N
normal (0)
object_name
character string
R
N
N
"E3POINT GGGG   AdXXX .Amin" where 
GGGG is the gas name and XXX  is the 
Modbus address.  Values for gas name 
include "CO" and "COMB".
out_of_service
boolean
R
C
N
FALSE
present_value
real
R
N
Y
Gas threshold less hysterisis.  
Synchronization is maintained with the 
301C and the E3Point.  Whichever value is 
written last is distributed to the other two 
locations.
reliability
enumerated
O
C
N
no_fault_detected (0)
status_flags
in_alarm
boolean
R
C
N
always false (0)
fault
boolean
R
C
N
always false (0)
overridden
boolean
R
C
N
always false (0)
out_of_service boolean
R
C
N
always false (0)
units
enumerated
R
C
N
ppm (96) or %  (98)
object_identifier
R
N
N
Modbus address * 256 + 3.  For example an 
E3Point at Modbus address 009 will appear 
as 2307 or 0x0903.
object_type
enumerated
R
C
N
analog_value (2)
event_state
enumerated
R
C
N
normal (0)
object_name
character string
R
N
N
"E3POINT GGGG   AdXXX .Amax" where 
GGGG is the gas name and XXX  is the 
Modbus address.  Values for gas name 
include "CO" and "COMB".
out_of_service
boolean
R
C
N
FALSE
present_value
real
R
N
Y
Gas threshold.  Synchronization is 
maintained with the 301C and the E3Point.  
Whichever value is written last is 
distributed to the other two locations.
reliability
enumerated
O
C
N
no_fault_detected (0)
status_flags
in_alarm
boolean
R
C
N
always false (0)
fault
boolean
R
C
N
always false (0)
overridden
boolean
R
C
N
always false (0)
out_of_service boolean
R
C
N
always false (0)
units
enumerated
R
C
N
ppm (96) or %  (98)
Notes
1  --  'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 --  'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM.
continued…