Fujitronic UG520H-x ユーザーズマニュアル

ページ / 275
2 - 17
7 MITSUBISHI PLC 
 1
Port
Transmission
Control Mode
RS-232C
RS-422
MODE1
MODE5
Trans. Mode 1
Trans. Mode 1
19200bps
Even
7 (ASCII)
Baud Rate
Parity
Transmission
Code
Data Length
Stop Bit
1
Sumcheck
Write while running
Terminal Resistor at Sender
Terminal Resistor at Receiver
Item
Setting of PLC
0
19200bps
Even
7
1
*
 1
0 for both STATION  x10 and  x1
Comm. Parameter of POD
Provided (fixed)
Available (fixed)
Provided (fixed)
Provided (fixed)
Communication Setting
The recommended communication parameter setting of both PLC and POD is as follows:
A series link unit
*1 Mode 1: without CR/LF, Mode 4: with CR/LF
If [Trans. Mode 4] is selected from [Trans. Mode] in [Comm. Parameter] of the panel editor,
specify [MODE4] in case of RS-232C, or select [MODE8] in case of RS-422.
Q series link unit
Port
Transmission
Control Mode
RS-232C
RS-422
When QnA series link is connected:
 
MODE5 (Binary Mode) (fixed).
When QnH(Q) series link is connected:
 
MC Protocol Type 5 (fixed).
0 for both STATION X 10 and X1
19200bps
Even
8 (fixed)
Provided (fixed)
Available (fixed)
Baud Rate
Parity
Transmission
Code
Data Length
Stop Bit
1
Sumcheck
Write while running
Item
Setting of PLC
0
19200bps
Even
1
Comm. Parameter of POD
Q00/Q01 CPU
When connecting the POD to the tool port of Q00 or Q01 CPU, it is neccessary to specify [serial
communication] setting on PLC parameter.  Note on the following setting.
UG00S-CW
Select [QnH(Q) series link] in [PLC type].
GX Developer (Application software for programming MITSUBISHI PLCs)
1. Double click [PLC parameter].
2. Click the [Serial] tab menu of the [Qn(H) Parameter] dialog.
3. Check [Use serial communication] to specify communication parameters such as Baud rate,
Sum check, etc.