SETTINGS AND PROCEDURES BEFORE 
OPERATION
5.4 Wiring
5.4.1 Precautions for safety devices and wiring
5
 - 28
1
O
V
ER
VI
E
W
2
S
YST
EM
 
CONF
IGURA
T
ION
3
S
P
E
C
IF
ICA
T
IONS
4
F
UNCT
IO
NS
5
S
E
T
T
INGS
 A
ND 
PR
O
C
E
DURES
 BEF
ORE 
OP
E
R
A
T
ION
6
T
R
O
U
BL
ESH
O
O
T
ING
AP
PENDI
X
(7) Safety devices to be connected
Connect safety devices that meet the conditions as shown below.
(a) Push button switch for emergency stop
The switch that has the direct opening action (positive opening mechanism) and 
complies with EN60947-5-1 or IEC60947-5-1.
(b) Door interlock switch
The switch that has the direct opening action (positive opening mechanism) and 
complies with EN60947-5-1 or IEC60947-5-1.
(c) Light curtain/beam sensor switch
The switch that has reliable performance so that it can satisfy the required control 
category.
The input P type of the safety relay module does not have the channel-to-channel 
short-circuit diagnostics function for light curtain. Therefore, when a light curtain is 
used and it needs to comply with Category 4, the light curtain must be Type 4 of 
IEC/ EN61496-1.
(8) Connecting safety devices 
The same safety device cannot be input to multiple modules.
Also, start-up input cannot be input to multiple input modules.
Figure 5.17 Connecting safety devices
COM
X1
X0
COM
24V IN
0V IN
Control 
output 2
Control 
output 1
X0
X1
COM
X1
X0
COM
X0
X1
COM
X1
X0
COM
X0
X1
Safety relay module
Safety relay module
Safety relay module
Safety relay module
COM
X1
X0
COM
X0
X1
24VDC
Safety switch
Safety light curtain