Analog Deadband Adjustment
100K or higher potentiometer. Figure 66 shows how the output voltage varies at the vari-
ous potentiometer positions, for three typical potentiometer values. Note that the effect is 
an exponentiation that will cause the motors to start moving slowly and accelerate faster 
as the potentiometer reaches either end. 
This curve is actually preferable for most applications. It can be corrected or amplified by 
changing the controller’s exponentiation parameters (see “Command Control Curves” on 
page 42
.
Analog Deadband Adjustment
The controller may be configured so that some amount of potentiometer or joystick travel 
off its center position is required before the motors activate. The deadband parameter can 
be one of 8 values, ranging from 0 to 7, which translate into a deadband of 0% to 16%. 
Even though the deadband will cause some of the potentiometer movement around the 
center position to be ignored, the controller will scale the remaining potentiometer move-
ment to command the motors from 0 to 100%. 
Note that the scaling will also cause the motors to reach 100% at sightly less than 100% of 
the potentiometer’s position. This is to ensure that 100% motor speed is achieved in all cir-
cumstances. Table 22 below shows the effect of the different deadband parameter values. 
Changing the deadband parameter can be done using the controller’s switches (see “Con-
figuring the Controller using the Switches” on page 153) 
or the Roborun utility on a PC (see 
“Loading, Changing Controller Parameters” on page 162).