Serial (RS-232) Controls and Operation
90
AX2500/2850 Motor Controller User’s Manual
 Version 1.7. February 1, 2005
Communication Settings
The AX2500/2850 serial communication port is set as follows:
9600 bits/s, 7-bit data, 1 Start bit, 1 Stop bit, Even Parity
Communication is done without flow control, meaning that the controller is always ready 
to receive data and can send data at any time.
These settings cannot be changed. You must therefore adapt the communication setting 
in your PC or microcomputer to match those of the controller.
Establishing Manual Communication with a PC
The controller can easily be connected to a PC in order to manually exercise its capabilities. 
Simply connect the supplied cable to the AX2500/2850 on one end (DB-15 connector) and 
to a free COM port on the other end (DB-9 connector).
Once connected, you will need a Terminal Emulation program to display the data received 
from the controller on the PC’s screen and to send characters typed on the keyboard to the 
controller. All Windows PC’s come with the Hyperterm terminal emulation software.
Locate the Hyperterm launch icon in the Start button: Programs > Accessories > Commu-
nication folder.
You will need to configure Hyperterm to use the COM port to which you have connected 
the controller (typically COM1) and to configure the communication settings as described 
in the section above.
To save time and avoid errors, a hyperterm configuration file is automatically installed in 
your PC’s Start button menu when you install Roboteq’s Roborun utility (See “Downloading 
1
2
3
4
7
8
9
5
1
2
3
4
5
6
7
8
9
6
TX Data
RX Data
Data Out
Data In
GND
GND
DB9 Female
DB9 Male
FIGURE 58. RS232 extension cable/connector wiring diagram