Mitsubishi Electronics AJ65SBT-64AD ユーザーズマニュアル

ページ / 74
5 - 3
MELSEC-A
5   PROGRAMMING
(1)   Program example for power-on
Initial 
settings of 
master 
station
Read of 
remote 
input 
signals
Checking 
of 
AJ65SBT-
64AD
status
Initial 
settings
Error LED
Read of 
digital 
values
Number of connected 
modules: 1
Writes to master station
AJ65SBT-64AD station 
information (remote device 
station, 1 station occupied, 
station No. 1)
Writes to master station
Refresh directive
Data link started by 
buffer memory
Turns off start request 
signal at normal completion
of start.
Reads parameter status at 
abnormal completion of start.
Turns off start request signal 
at abnormal completion of start.
RXn0 to RX(n+1)F are read to 
X100 to X11F
Reads data link status.
AJ65SBT-64AD data link 
normal
AJ65SBT-64AD data link 
abnormal
CH.1, CH.2: A/D conversion 
enabled
CH.1: 0 to 5V
CH.2: User range setting 1
CH.2 moving average 
processing count: 16 times
Writes to master station.
Turns on CH.2 moving average
processing specifying flag.
Turns on initial data processing
completion flag.
Turns on initial data setting 
request flag.
Turns off initial data processing
completion flag.
Turns off initial data setting 
request flag.
Reads CH.1 digital value.
Reads CH.2 digital value.