5 - 8
MELSEC-A
5   PROGRAMMING
(1)   Program example for power-on
Setting of 
network 
parameters
Setting of 
automatic 
refresh 
parameters
Synchronization 
mode invalid
Dedicated instruction 
(RLPA)
Starting I/O number of 
master module
Parameter storage 
starting device
Device which turns on 1 
scan at completion
Reads parameter status 
at abnormal completion.
Sets RX starting number.
Sets "X".
Sets X100.
Sets RY starting number.
AJ65SBT-64AD station
information (remote 
device station, 1 station 
occupied, station No. 1)
Number of connected
modules:1
Sets 32 points.
Sets "Y".
Sets Y100.
Sets 32 points.
Sets RW starting number.
Sets "D".
Sets D200.
Sets 260 points.
Sets SB starting number.
Sets "B".
Sets B0.
Sets 512 points.
Sets SW starting number.
Sets W0.
Sets "W".