7 ONLINE MODULE CHANGE
7.3.5 When user range setting is used and initial setting was made with sequence program
(other system is available)
(1) Conversion disable
(a)
Set the A/D conversion enable/disable setting (buffer memory address 0:
Un\G0) for all channel conversion disable and turn Operation Condition
Setting Request (Y9) from OFF to ON to stop conversion.
Un\G0) for all channel conversion disable and turn Operation Condition
Setting Request (Y9) from OFF to ON to stop conversion.
(2) Dismounting of module
(a)
After choosing [Diagnosis] - [Online module change] on GX Developer to
enter the "Online module change" mode, double-click the module to be
changed online to display the "Online module change" screen.
enter the "Online module change" mode, double-click the module to be
changed online to display the "Online module change" screen.