Mitsubishi Electronics Q68ADI ユーザーズマニュアル

ページ / 140
3 - 2                                                                                                                                                       3 - 2
MELSEC-Q
3   SPECIFICATIONS
 3
Model name
Item
Q64AD
Q68ADV
Q68ADI
Conversion speed
80 
 s/channel
(When there is temperature drift, the time calculated by adding 160 
 s will be used
regardless of the number of channels used)
Absolute maximum input
Voltage : ± 15 V     Current : ± 30 mA
E
2
PROM write count
Max. 100 thousand times
Insulation method
Between the I/O terminal and PLC power supply : Photocoupler insulation
                    Between channels : Non-insulated
Dielectric withstand voltage
Between the I/O terminal and PLC power supply: 500VAC for 1 minute
Insulation resistance
Between the I/O terminal and PLC power supply: 500VDC 20M  or more
Number of occupied points
16 points
Connection terminals
18-point terminal block
Applicable wire size
0.3 to 0.75 mm
2
Applicable solderless terminal
R1.25-3 (A solderless terminal with sleeve cannot be used)
Internal current consumption
(5 V DC)
0.63 A
0.64 A
0.64 A
Weight
0.18 kg
0.19 kg
0.19 kg
REMARK
See the user’s manual for the CPU module being used for general specifications of
the A/D converter modules.
3.1.2 I/O conversion characteristic
The I/O conversion characteristic represents the angle formed by a straight line
connecting the "offset value" and "gain value" when the analog signals (voltage or
current input) from outside the PLC are converted to digital values.
Offset value
The offset value denotes the analog input value (voltage or current) that makes the
digital output value 0.
Gain value
The gain value denotes the analog input value (voltage or current) that makes the
digital output value:
4000   (in normal resolution mode)
12000 (when 0 to 5 V, 1 to 5 V, 4 to 20 mA, 0 to 20 mA or the user range setting is
selected in high resolution mode)
16000 (when -10 to 10 V or 0 to 10 V is selected in high resolution mode).