Mitsubishi Electronics Q68ADI ユーザーズマニュアル

ページ / 140
3 - 12                                                                                                                                                       3 - 12
MELSEC-Q
3   SPECIFICATIONS
3.2.2 Maximum and minimum values hold function
(1)   The maximum and minimum digital output values for each channel are stored in buffer
memory addresses 30 to 45 (Un\G30 to Un\G45).
(2)   When the operating condition setting completed flag (X09) turns OFF, the values
are cleared to 0 and new maximum and minimum values are stored when
conversion begins.
(3)   Since the area for storing the maximum and minimum values can be rewritten with
the sequence program, the maximum and minimum values within a specific period
of time can be checked.
3.3 I/O Signals for the PLC CPU
3.3.1 List of I/O signals
Table 3.3 shows a list of the I/O signals for the A/D converter modules.
Note that I/O numbers (X/Y) shown in this chapter and thereafter are the values when
the start I/O number for the A/D converter module is set to 0.
Table 3.3 List of I/O signal
Signal direction CPU   A/D converter module
Signal direction CPU 
 A/D converter module
Device No. (Input)
Signal name
Device No. (Output)
Signal name
X0
Module READY
Y0
X1
Temperature drift compensation flag
Y1
X2
Y2
X3
Y3
X4
Y4
X5
Y5
X6
Y6
X7
Y7
X8
Use prohibited 
1
Y8
Use prohibited 
1
X9
High resolution mode status flag
Y9
Operating condition setting request
XA
Offset/gain setting mode flag
YA
User range write request
XB
Channel change completed flag
YB
Channel change request
XC
Use prohibited 
1
YC
Use prohibited 
1
XD
Maximum value/minimum value reset
completed flag
YD
Maximum value/minimum value reset
request
XE
A/D conversion completed flag
YE
Use prohibited 
1
XF
Error flag
YF
Error clear request
POINT
1  These signals cannot be used by the user since they are for system use only.
If these are turned ON/OFF by the sequence program, the functioning of the
A/D converter module cannot be guaranteed.