MELSEC-Q
4   SETUP AND PROCEDURES BEFORE OPERATION
4.4.2 External wiring
(1)   Q64AD
GND
 1   Shielded
V +
I +
V –
SLD
+ 15 V
– 15 V
 5
A.G.
FG
 4
ANALOG    
GND
250 
 2
GND
500 k
 1   Shielded
 2
 3
+ 15 V
– 15 V
500 k 
500 k 
V +
I +
V –
SLD
500 k 
(a)  For voltage input
       Signal source 0 to ± 10 V
(b)  For current input
      Signal source 0 to ± 20 mA
1  Use a twisted two core shielded wire for the power wire.
2  Shows input resistance of Q64AD.
3  If current input, always connect to (V +) and (I +) terminals.
4  "A.G." terminal does not normally require wiring.  However, it can be used as GND
for compatible equipment ground under the following conditions.
(1)   When there is a difference in polarity between "A.G" and "GND for compatible
equipment".
(2)   As an alternative for 0 V input when only the + side is open on a ± wire.
5  Always use a ground.  In addition, ground the FB of the power supply module.