Mitsubishi Electronics Q68ADI ユーザーズマニュアル

ページ / 140
7 - 3                                                                                                                                                       7 - 3
MELSEC-Q
7   ONLINE MODULE CHANGE
7.3 Online Module Change Procedure
There are the following online module change procedures depending on whether the
user range setting has been made or not, whether the initial setting of GX Configurator-
AD has been made or not, and whether the other system exists or not.
Range setting
Initial setting
Other system
Reference section
Industrial shipment setting
GX Configurator-AD
Section 7.3.1
Industrial shipment setting
Sequence program
Section 7.3.2
User range setting
GX Configurator-AD
Present
Section 7.3.3
User range setting
GX Configurator-AD
Absent
Section 7.3.4
User range setting
Sequence program
Present
Section 7.3.5
User range setting
Sequence program
Absent
Section 7.3.6
7.3.1 When industrial shipment setting is used and initial setting was made with GX
Configurator-AD
(1)   Conversion disable
(a)
Set the A/D conversion enable/disable setting (buffer memory address 0:
Un\G0) for all channel conversion disable and turn Operation Condition
Setting Request (Y9) from OFF to ON to stop conversion.