Toshiba LF410/LF602 사용자 설명서

다운로드
페이지 16
LF410/LF600  LF410/LF602 
2
 
Fluid conductivity: 5µS/cm minimum 
Fluid temperature:  
–10 to +180
°C : Ceramic type   
(14 to 356 
°F)  
Note : 120
°C (248°F) above is separate type 
–10 to +120
°C : tefolon PFA 
(14 to 248
°F) 
Ambient temperature:  
Without cFMus Approval: 
-20  to  + 60 °C (-4 to 140 °F) 
With cFMus Approval: 
-10 to  +45°C (14 to 113 °F) 
Structure: NEMA 4X (IP 67) Watertight 
Power consumption:  
17W(27VA) or less 
19W(29VA) or less (with PROFIBUS) 
Conformance to European Community Directives: 
EMC directive 89/336/EEC 
The low voltage 93/68/EEC 
PED 97/23/EC (Note 1) 
Note : See table 2 for detail.
 
Approved hazardous location certifications: 
Model: LF414/LF600 and LF414/LF602 
cFMus explosion proof: 
FM Class I, Division 2, Groups A,B,C, and D. 
FM Class II, Division 2, Groups E, F and G. 
FM Class III. 
Detector and converter combination: 
LF410/LF600: Combined type for standard 
specification. 
LF410/LF602: Separate type for standard 
specification. 
LF414/LF600: Combined type with Ex approval 
of Class I, Division 2 (cFMus). 
LF414/LF602: Separate type with Ex approval  
of Class I, Division 2 (cFMus). 
 
 Model LF410 and LF414 Detectors 
Mounting style: Wafer type 
Fluid pressure: -0.1 to 2.0MPa  
(-15 to 300psi, or -1.0 to 20 bar) 
Note: The test pressure before shipping from the factory 
is equal to twice the nominal pressure rating of the 
customer specified flange connection during 15 
minutes. 
Connection flange standards: ANSI 150, ANSI 
300, BS10 and 16, DIN PN10 and PN16, JIS10K, 
JIS16K and JIS20K 
Principal materials: 
Case — 25 to 100mm (1” to 4”): stainless steel 15, 
150, and 200mm (1/2”, 6”, and 8”): carbon 
steel 
Linings — 15 to 100mm (1/2” to 4”): Ceramic 
tube (std.) & teflon PFA (opt.) 
150 and 200mm (6” to 8”): teflon PFA 
Electrodes — 316L stainless steel (std.) 
Grounding rings — 316 stainless steel (std.) 
Note:  See Table 3 for optional materials and other 
related information. 
Measuring tube material  304 stainless steel 
(in case of Teflon PFA lining) 
Coating — 25 to 100mm (1” to 4”): no coating 
(stainless steel body). 
15, 150, and 200mm (1/2”, 6”, and 8”): 
phthalic acid resin coating with pearl-gray 
colored. 
Heat shock resistance : for a ceramic tube detector 
Heating: 
ΔT ≤ 150 
°
C/0.5sec (302
°
F/0.5sec) 
Cooling: 
ΔT ≤ 100 
°
C/0.5sec (212
°
F/0.5sec) 
Note:   The above means that the ceramic tube detector 
withstands the shock of sudden heating 
(temperature difference 150
°C or less per 
0.5seconds) and sudden cooling (temperature 
difference 100
°C or less per 0.5seconds). 
Dimensions and weights: See Figures 3 to 8. 
Cable connection port: for separate type detectors. 
Cable glands — 
LF410:  without cFMus approval 
Provided as standard 
R(PT) 1/2 male screws. 
LF414:  with cFMus approval 
Not provided 
3/4-14NPT male screws are required. 
Applicable diameter — 11 to 13mm  
(0.433 to 0.512 inch) 
 
 Model LF600 and LF602 converters 
Input signals 
Analog signal — the voltage signal from detector, 
proportional to process flow rate (for LF602 
separate type converter). 
Digital input DI (opt.) 
Signal type: 20 to 30Vdc voltage signal 
Input resistance: 2.7k
Ω 
Number of inputs: one point 
DI function — One of the following functions can 
be assigned to the optional DI signal. 
Range switching — Selects either the higher or 
lower range in the unidirectional or 
bidirectional 2-range setting. 
Totalizer control — Starts and stops the built-in